Board Report November 2025
11/3/25, 9:23 AM
Violation / Work Item Listing
Estimated Completion Date
Item I.D.
Location(s) (Room No)
Rule Violated
Description of the violation
Recommendation to correct violation
Action I.D.
Priority Code
Estimated Cost
ISBE Adjustment
Funding Type
Specification(s) Units Of Measure
Quantity Labor Code
110.26
opened
Elect. Equip. Furnish and Install missing component
missing cover or seal open conduit Non-GFI type receptacle adjacent to a water source Panels Blocked cannot be opened Safety concern with panel locking mechanism Damaged Exit Sign Safety concern with damaged panel front (exposed bus) Emergency Lighting fixture is not wired to ambient lighting circuit used in space. Emergency Lighting fixture is not wired to ambient lighting circuit used in space. Missing Exit Sign Non-GFI type receptacle adjacent to a water source Emergency Lighting fixture is not wired to ambient lighting circuit used in space. missing cover or seal open conduit Use of extension cords is prohibited No AF labeling on electrical panels No vacuum breaker on the hot/cold hose connection
provide cover or seal open raceway, box, etc.
67 Classroom 104 NFPA 70 300.21
f
b.
ea
12
2
$2,400.00
8/15/2030 F
175.610, NFPA 70 210 175610, NFPA 70 110.26 175.610, NFPA 70 "175.480, 175.670 175.670" 175.610, NFPA 70 110.12
replace receptacle with GFI type.
GFI Receptacle
68 Serving 150C
f
c.
ea
1
2
$200.00
8/15/2035 O
3" Clear space in front of Elect. Equip.
Remove blocking equipment
69 Mech. 151
f
c.
ea
2
1
$200.00
8/15/2035 O
install full height panel cover c
Match panel manufacturer ea
70 Mech. 151
c.
1
2
$1,000.00
8/15/2035 F
Provide Exit Sign
71 Beachers 217
Provide Exit Sign
f
a.
ea
2
2
$1,500.00
8/15/2026 F
replace interior panel cover
Match panel manufacturer ea
72 Practice 310
c
c.
1
2
$1,000.00
8/15/2035 F
175.680, NFPA 101 Chap. 7
rework ambient light branch circuit ahead of switching device.
Rework ltg circuit
73 Chorus 210
f
a.
ea
1
2
$1,500.00
8/15/2026 F
175.680, NFPA 101 Chap. 7 "175.480, 175.670 175.670" 175.610, NFPA 70 210
rework ambient light branch circuit ahead of switching device.
Rework ltg circuit
74 Stair S102
f
a.
ea
1
2
$750.00
8/15/2026 F
Provide Exit Sign
75 Kitchen 150
Provide Exit Sign
f
a.
ea
1
2
$1,000.00
8/15/2026 F
replace receptacle with GFI type.
GFI Receptacle
76 Corridor C103
f
c.
ea
7
2
$1,400.00
8/15/2035 O
175.680, NFPA 101 Chap. 7
rework ambient light branch circuit ahead of switching device. provide cover or seal open raceway, box, etc. Remove extension cord(s) Arc Flash Study Assessment, Study, Report and Labels Provide utility faucet with vacuum breaker f f f f f
Rework ltg circuit
77 Study Hall 140
a.
ea
1
2
$750.00
8/15/2026 F
Furnish and Install missing component
78 Study Hall 140 NFPA 70 300.21
b.
ea
1
2
$200.00
8/15/2030 F
175.610.b, NFPA-70 400.12
Remove extension cord(s)
79 Classroom 136
b.
ea
1
1
$200.00
8/15/2030 F
175.610 NFPA 70 110.16
Complete AF Study Provide utility faucet with Provide backflow prevention device for the Ice Maker Provide floor drains draining to an Oil Intereceptor or Holding Tank. Replace trough urinals with multiple single urinals vacuum breaker Provide ventilation to remove heat and fumes during kiln operation Replace or correct sink waste piping to
80 Bldg Wide panels
c.
ea
1
2
$60,000.00
8/15/2030 O
IL Plumbing Code 890.1130 IL Plumbing Code 890.1130, f, 1 IL Plumbing Code 890.520, c IL Plumbing Code 890.660, c
81 Carts 150H
a.
ea
1
2
$1,000.00
8/15/2026 O
No Backflow device on Ice Maker
Provide backflow prevention device for the Ice Maker
82 2024 100X
f
b.
ea
1
2
$1,000.00
8/15/2030 O
Provide floor drains draining to an Oil
No Oil Interceptor
83 Auto Mechanics 118A 118A
f
b.
ea
1
2
$13,000.00
8/15/2030 O
Intereceptor or Holding Tank.
Natatorium Lobby Men's Toilet
Replace trough urinals with multiple single urinals b Provide ventilation to remove heat and fumes during kiln operation f
Trough Urinals are Prohibited
84
b.
LS
1
2
$15,000.00
8/15/2030 O
No Ventilation provided for one of the kilns Multiple sinks in Home Ec.Room showed signs of leaks from trap
2012 IMC, 923.1.1
85 Graphic Arts 13
b.
ea
1
2
$5,000.00
8/15/2030 F
86 Home Ec. #110 IL Plumbing Code 890.XXXX
Replace or correct sink waste piping to eliminate leaks.
f
b.
ea
1
1
$5,000.00
8/15/2030 O
https://apps.isbe.net/HLSWeb/ScheduleItemListing.aspx?surveyId=19573
5/6
Made with FlippingBook - professional solution for displaying marketing and sales documents online