Board Report November 2025

11/3/25, 9:23 AM

Violation / Work Item Listing

Estimated Completion Date

Item I.D.

Location(s) (Room No)

Rule Violated

Description of the violation shall be directly connected to a permanently installed receptacle. Non-GFI type receptacle adjacent to a water source Emergency Lighting fixture is not wired to ambient lighting circuit used in space. Damaged raceway for power and/or communications, improper support, etc. Use of extension cords is prohibited Non-GFI type receptacle adjacent to a water source Missing Exit Sign (access to ext. kitchen) Panels Blocked cannot be opened Safety concern with damaged panel front Emergency Lighting fixture is not wired to ambient lighting circuit used in space. Use of extension cords is prohibited Missing Exit Sign Non-GFI type receptacle adjacent to a water source Emergency Lighting fixture is not wired to ambient lighting circuit used in space. Non-GFI type receptacle adjacent to a water source Non-GFI type receptacle adjacent to a water source Panels Blocked cannot be Missing Exit Sign Missing Exit Sign Emergency Lighting fixture is not wired to ambient lighting circuit used in space. Missing Exit Sign

Recommendation to correct violation

Action I.D.

Priority Code

Estimated Cost

ISBE Adjustment

Funding Type

Specification(s) Units Of Measure

Quantity Labor Code

175.610, NFPA 70 210

replace receptacle with GFI type.

GFI Receptacle

47 Classroom 119

f

c.

ea

1

2

$200.00

8/15/2035 O

175.680, NFPA 101 Chap. 7

rework ambient light branch circuit ahead of switching device.

Rework ltg circuit

48 Classroom 120

f

a.

ea

1

2

$750.00

8/15/2026 F

175.610, NFPA 70 300 (incl. 300.4, 300.11) 175.610.b, NFPA-70 400.12 175.610, NFPA 70 210 "175.480, 175.670 175.670" 175610, NFPA 70 110.26 "175.480, 175.670 175.670" 175.680, NFPA 101 Chap. 7 175.480, 175.670 175.670 175.610, NFPA 70 110.12 175.680, NFPA 101 Chap. 7

replace damaged/unsupported wiremold sections with metal conduit systems f

Replace wiremold with conduit systems

49 Bldg Wide misc.

b.

LS

50

2

$10,000.00

8/15/2030 F

Remove extension cord(s) GFI Receptacle

Remove extension cord(s)

50 Classroom 121

f

b.

ea

2

1

$400.00

8/15/2030 F

replace receptacle with GFI type.

51 Classroom 120B

f

c.

ea

1

2

$200.00

8/15/2035 O

Provide Exit Sign

52 Stores 122, 122B

Provide Exit Sign

f

a.

ea

2

2

$2,000.00

8/15/2026 F

3" Clear space in front of Elect. Equip.

Remove blocking equipment

53 Stores 122B

f

c.

ea

2

1

$200.00

8/15/2035 O

Provide Exit Sign

54 Corridor C114

Provide Exit Sign

f

a.

ea

1

2

$1,000.00

8/15/2026 F

rework ambient light branch circuit ahead of switching device.

Rework ltg circuit

55 Classroom 169

f

a.

ea

2

2

$1,500.00

8/15/2026 F

Provide Exit Sign

56 Corridor C131

Provide Exit Sign

f

a.

ea

1

2

$1,000.00

8/15/2026 F

replace interior panel cover

Match panel manufacturer

57 Corridor C131

c

c.

ea

1

2

$1,000.00

8/15/2035 F

rework ambient light branch circuit ahead of switching device.

Corridor adj. 167C

Rework ltg circuit

58

f

a.

ea

1

2

$750.00

8/15/2026 F

175.480, 175.670 175.670

Provide Exit Sign

59 Admin. Area misc.

Provide Exit Sign

f

a.

ea

4

2

$4,000.00

8/15/2026 F

175.610.b, NFPA-70 400.12

Remove extension cord(s)

Remove extension cord(s)

60 Library 158

f

b.

ea

1

1

$200.00

8/15/2030 F

175.480, 175.670 175.670 175.610, NFPA 70 210

Provide Exit Sign

61 Library 158

Provide Exit Sign

f

a.

ea

1

2

$1,000.00

8/15/2026 F

Audio Visual 158A

replace receptacle with GFI type.

GFI Receptacle

62

f

c.

ea

1

2

$200.00

8/15/2035 O

175.680, NFPA 101 Chap. 7

rework ambient light branch circuit ahead of switching device.

Rework ltg circuit

63 Math 116

f

a.

ea

1

2

$750.00

8/15/2026 F

175.610, NFPA 70 210 175.610, NFPA 70 210 175610, NFPA 70

replace receptacle with GFI type.

GFI Receptacle

64 Science 114

f

c.

ea

7

2

$1,400.00

8/15/2035 O

GFI Receptacle (install Quad) 3" Clear space in front of

Old Boiler Room 157

replace receptacle with GFI type. Remove blocking equipment

65

f

c.

ea

1

2

$400.00

8/15/2035 O

66 Old Boiler Room 157

f

c.

ea

1

1

$2,000.00

8/15/2035 F

https://apps.isbe.net/HLSWeb/ScheduleItemListing.aspx?surveyId=19573